Section 11
Device and functionality tests
294
Table 205:
Contact tests
Description
Make and carry
Breaking capacity for DC, L/R
≤40 ms
Mechanical durability
Table 206:
Insulation tests
1)
Description
Dielectric tests
Impulse voltage tests
Insulation resistance
measurements
1) Insulation tests are not applicable to SIM8F/SIM4F
Table 207:
Electromagnetic compatibility and immunity tests
Description
Electrostatic discharge
•
Air discharge
Radio frequency
electromagnetic field (amplitude
modulated)
Radio frequency
electromagnetic field from digital
radio telephones (pulse
modulated)
Power frequency (50 Hz)
magnetic field
•
Continuous
•
3 s
Table continues on next page
Type test value
Signaling contacts
•
5 A, continuous
•
10 A for 3 s
•
15 A for 0.5 s
Signaling contacts
•
48 V, 1.00 A
•
110 V, 0.25 A
•
220 V, 0.15 A
10000 operations
Type test value
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min for
communication
2.8 kV DC, 1 min
700 V DC, 1 min for
communication
5 kV, 1.2/50 μs, 0.5 J
>100 MΩ, 500 V DC
Type test value
8 kV
10 V/m (RMS)
f = 80...1000 MHz and 1.4...2.7
GHz
10 V/m (RMS)
f = 900 MHz, 1890 MHz
100 A (RMS)/m
300 A (RMS)/m
Installation and Commissioning Manual
1MRS757488 H
Reference
IEC 60255-1, IEC 61810-1 and
IEEE C37.90-2005
IEC 60255-1, IEC 61810-1 and
IEEE C37.90-2005
IEC 60255-1, IEC 61810-1 and
IEEE C37.90-2005
Reference
IEC 60255-27 and IEEE
C37.90-2005
IEC 60255-27 and IEEE
C37.90-2005
IEC 60255-27
Reference
IEC 60255-26 and IEC
61000-4-2, Level 3
IEC 60255-26 and IEC
61000-4-3, Level 3
IEC 61000-4-3, Level 3
IEC 60255-26 and IEC
61000-4-8
RIO600