ABB Remote I/O RIO600 Installation And Commissioning Manual page 302

Table of Contents

Advertisement

Section 11
Device and functionality tests
294
Table 205:
Contact tests
Description
Make and carry
Breaking capacity for DC, L/R
≤40 ms
Mechanical durability
Table 206:
Insulation tests
1)
Description
Dielectric tests
Impulse voltage tests
Insulation resistance
measurements
1) Insulation tests are not applicable to SIM8F/SIM4F
Table 207:
Electromagnetic compatibility and immunity tests
Description
Electrostatic discharge
Air discharge
Radio frequency
electromagnetic field (amplitude
modulated)
Radio frequency
electromagnetic field from digital
radio telephones (pulse
modulated)
Power frequency (50 Hz)
magnetic field
Continuous
3 s
Table continues on next page
Type test value
Signaling contacts
5 A, continuous
10 A for 3 s
15 A for 0.5 s
Signaling contacts
48 V, 1.00 A
110 V, 0.25 A
220 V, 0.15 A
10000 operations
Type test value
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min for
communication
2.8 kV DC, 1 min
700 V DC, 1 min for
communication
5 kV, 1.2/50 μs, 0.5 J
>100 MΩ, 500 V DC
Type test value
8 kV
10 V/m (RMS)
f = 80...1000 MHz and 1.4...2.7
GHz
10 V/m (RMS)
f = 900 MHz, 1890 MHz
100 A (RMS)/m
300 A (RMS)/m
Installation and Commissioning Manual
1MRS757488 H
Reference
IEC 60255-1, IEC 61810-1 and
IEEE C37.90-2005
IEC 60255-1, IEC 61810-1 and
IEEE C37.90-2005
IEC 60255-1, IEC 61810-1 and
IEEE C37.90-2005
Reference
IEC 60255-27 and IEEE
C37.90-2005
IEC 60255-27 and IEEE
C37.90-2005
IEC 60255-27
Reference
IEC 60255-26 and IEC
61000-4-2, Level 3
IEC 60255-26 and IEC
61000-4-3, Level 3
IEC 61000-4-3, Level 3
IEC 60255-26 and IEC
61000-4-8
RIO600