ABB Remote I/O RIO600 Installation And Commissioning Manual page 57

Table of Contents

Advertisement

1MRS757488 H
RIO600
Installation and Commissioning Manual
SCM8H / SCM8L
0V-
DI 1
DI1
DI 2
DI2
DI3
DI 3
DI4
DI 4
0V-
-
HS1
HS1
HS2
HS2
HS3
HS3
HS4
HS4
+
GUID-732CEDBB-5677-4C61-9598-ED1BB4A28C01 V2 EN
Figure 27:
Connection diagram for three-position switch application (rod type
with DC motor)
Table 15:
SCM connection for three-position switch application
X1
Connector
inputs
OV-
1
DI1
2
DI2
3
DI3
4
DI4
5
OV-
6
X1
1
COM for DI1 and DI2
2
Earthing switch CLOSE
3
Earthing switch OPEN
4
Disconnector CLOSE
5
Disconnector OPEN
6
COM for DI3 and DI4
X2
1
L-
2
3
M
4
5
6
L+
Description
X2
Common
-
return for DI1
and DI2
Earthing
HS1
switch CLOSE
position signal
Earthing
HS2
switch OPEN
position signal
Disconnector
HS3
switch CLOSE
position signal
Disconnector
HS4
switch OPEN
position signal
Common
+
return for DI3
and DI4
Section 5
Installing
Connector
Description
outputs
1
AUX. DC
voltage L-
2
DC motor
connection
3
DC motor
connection
4
DC motor
connection
5
DC motor
connection
6
AUX. DC
voltage L+
49