Table 28:

Operating parameter settings of SIM8F module

Parameter name
Frequency
Nominal current
Nominal voltage
Rated sensor current
Io signal sel
Phase Rotation
Sensor Correction Factors
Phase A
Current
Amplitude
Current Phase
Voltage
Amplitude
Voltage Phase
Phase B
Current
Amplitude
Current Phase
Voltage
Amplitude
Voltage Phase
Table continues on next page
RIO600
Installation and Commissioning Manual
Operating parameter settings of SIM8F module
Range
Unit
50
Hz
60
80...630
A
500...48000
V
80
A
250
Calculated Io
-
Measured Io
ABC
-
ACB
0.7000...1.3000
-
-3.0000...
deg
+3.0000
0.7000...1.3000
-
-3.0000...
deg
+3.0000
0.7000...1.3000
-
-3.0000...
deg
+3.0000
0.7000...1.3000
-
-3.0000...
deg
+3.0000
Step
Default
-
50 Hz
1
400
1
15000
-
80
-
Calculated Io
-
ABC
0.0001
1.0000
0.00025
0.000
0.0001
1.0000
0.00025
0.000
0.0001
1.0000
0.00025
0.000
0.0001
1.0000
0.00025
0.000
Section 6
Commissioning
Description
Rated system
frequency
Nominal phase
current
Nominal phase-
to-phase voltage
Rated primary
current of sensor
Selection used
for Io signal
Phase rotation
order
Amplitude
correction factor
for current
sensor, phase A
Phase correction
factor for current
sensor, phase A
Amplitude
correction factor
for voltage
sensor, phase A
Phase correction
factor for voltage
sensor, phase A
Amplitude
correction factor
for current
sensor, phase B
Phase correction
factor for current
sensor, phase B
Amplitude
correction factor
for voltage
sensor, phase B
Phase correction
factor for voltage
sensor, phase B
69