ABB Remote I/O RIO600 Installation And Commissioning Manual page 166

Table of Contents

Advertisement

Section 6
Commissioning
Table 101:
FPIPTOC Settings
Name
Values (Range)
Operation
Off
On
Residual Start Cur
1...100
EF Start Cur
1...100
Inst Start Cur
10...100
Angle Sector
10...90
Operate Delay Time
100...60000
Ratio EF to Res Cur
0.1-1.0
Start Delay Time
0...1000
Angle Offset Sector
10...90
Reset Delay Time
20...6000
Revert Time
300...1500
158
Signals
Table 99:
FPIPTOC Input signals
Name
Type
IA
SIGNAL
IB
SIGNAL
IC
SIGNAL
Table 100:
FPIPTOC Output signals
Name
FPIPTOC_Oper
FPIPTOC_Start
Settings
Unit
-
A
A
A
Deg
ms
ms
Deg
ms
ms
Default
0
0
0
Type
BOOLEAN
BOOLEAN
Step
Default
-
On
1
4
1
4
1
50
1
15
10
500
0.1
0.1
10
20
1
45
1
20
10
300
1MRS757488 H
Description
Phase A current, IA
Phase B current, IB
Phase C current, IC
Description
Fault passage indication
function is started.
Fault passage indication
function is operated.
Description
Operation Off/On
Residual current
start threshold
Earth-fault current
start threshold
Earth-fault current
threshold for
instantaneous start
condition
Phase angle sector
boundary threshold
for fault passage
Operate delay time
Ratio earth-fault
current to residual
current
Start delay
Phase angle offset
threshold for fault
passage indication
Reset Delay Time
Revert time for delta-
calculation
Installation and Commissioning Manual
RIO600

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents