Reporting Reserved Addresses - ABB Remote I/O RIO600 Installation And Commissioning Manual

Table of Contents

Advertisement

Section 7
Modbus TCP communication
7.1.29
Table 124:
Correlation between the function code and address range
Module
Data type
name
DOM4
Boolean
DIM8H/
Boolean
DIM8L
RTD4
Signed 16
bit channel
status
informatio
n
Channel
range
informatio
n
(unsigned
16)
AOM4
Signed 16
bit channel
status
informatio
n
SIM8F/
Readable
SIM4F
data
Boolean
Writeable
data
Boolean
Signed 32
bit Analog
data and
Signed 16
bit enum
SCM
Boolean
SSR
SSR1 and
SSR 2
unsigned
16 bit
informatio
n
Table continues on next page
182

Reporting reserved addresses

Considering RIO600 expansion, the Modbus point list depicts several addresses
reserved for future use. In the current implementation, if a 3X/4X read poll is made for
a Modbus address which is reserved for future use, the value "0" is reported to the
Modbus master. The Modbus master must be able to poll for a maximum number of
data points in one single poll and it should not return an exception in case a reserved
address region falls between two unreserved or currently assigned Modbus address
regions. However, during a write poll (4X), if a Modbus master is trying to write the
value to a Modbus address which is reserved for future use, an exception is returned
to the Modbus master.
0X
1X
Readable
Writeable
Readable
(FC 01)
(FC 05)
(FC 02)
Yes
Yes
No
No
No
Yes
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
No
No
3X
Writeable
Readable
Writeable
(FC 04)
No
Yes
No
No
Yes
No
No
Yes
No
No
Yes
No
No
Yes
No
No
Yes
No
No
Yes
No
No
Yes
No
No
Yes
No
No
Yes
No
Installation and Commissioning Manual
1MRS757488 H
4X
Readable
Writeable
(FC 03)
(FC 06)
Yes
Yes
Yes
No
Yes
No
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
RIO600