Functions Available In Sim8F - ABB Remote I/O RIO600 Installation And Commissioning Manual

Table of Contents

Advertisement

1MRS757488 H
Parameter name
Fault Indication Reset Method
Update Interval for Metering Values
New installation
6.1.6.1
RIO600
Installation and Commissioning Manual
Range
Unit
Self Reset
-
Method,
Definite Time,
Voltage
Presence,
DT or Voltage
Presence
1...15
-
-
-
Rated Sensor Current set as 80 A refers to 150 mV at 50 Hz and 180
mV at 60 Hz when 80 A is injected. Similarly, Rated sensor current
set as 250 A refers to 150 mV at 50 Hz and 180 mV at 60 Hz when 250
A is injected.

Functions available in SIM8F

Table 29:
Functions available in SIM8F
Function
Measurement functions
Three-phase current
measurement
Three-phase voltage
measurement
Residual current measurement
Table continues on next page
Step
Default
-
1
-
IEC 61850
Edition 1
Edition 2
CMMXU
CMMXU
VMMXU
VMMXU
RESCMMXU
RESCMMXU
Section 6
Commissioning
Description
Definite Time
Self Reset
Method: Flashing
protection
indication LED is
reset
immediately
once the fault is
cleared.
Definite Time:
Flashing
protection
indication LED is
reset after the
definite time set
by LED reset
time delay.
Voltage
Presence:
Flashing
protection
indication LED is
reset after the
presence of 3 ph
voltage.
DT or Voltage
Presence: ORing
of above two
methods.
4
Update interval
for metering
values × 500 ms
-
Performs reset of
energy counter
and internal
statistics
information
IEC 60617
IEC-ANSI
3I
3I
3U
3U
Io
Io
71