Rated Sensor Current set as 80 A refers to 150 mV at 50 Hz and 180
mV at 60 Hz when 80 A is injected. Similarly, Rated sensor current
set as 250 A refers to 150 mV at 50 Hz and 180 mV at 60 Hz when 250
A is injected.

Functions available in SIM4F

Table 98:
Functions available in SIM4F
Function

Measurement functions

Three-phase current
measurement
Residual current measurement
Current average and peak
measurement
Detection and indication functions
Three-phase non-directional
overcurrent fault detection
Non-directional earth-fault
detection
Negative-sequence overcurrent
protection
Three-phase inrush detector
Fault passage indicator
Measurement functions
Three-phase current measurement CMMXU
See
Measurement
functions.
Residual current measurement RESCMMXU
See
Measurement
functions.
Current peak measurement CMSTA
See
Measurement
functions.

Three-phase current fault detection

Three-phase non-directional overcurrent fault detection PHPTOC
See
Three-phase non-directional overcurrent fault detection
IEC 61850
Edition 1
Edition 2
CMMXU
CMMXU
RESCMMXU
RESCMMXU
CMSTA
CAVMMXU
CMAMMXU
RCAVMMXU
PHPTOC
PHPTOC
EFPTOC
EFPTOC
NSPTOC
NSPTOC
INRPHAR
INRPHAR
FPIPTOC
FPIPTOC
Section 6
Commissioning
IEC 60617
IEC-ANSI
3I
3I
Io
Io
-
-
3I>
51P
I0>
51N
I2>
46
3I2f>
68
-
-
PHPTOC.
149