Modbus TCP/IP diagnostic counters over Web HMI

Modbus TCP/IP diagnostic counters can be viewed via the WHMI. These counters
show the sent and received Modbus protocol link frames and Modbus errors.
Table 115:
TCP/IP diagnostic counters
Counter
Description
Received frames
Total amount of received Modbus frames.
Transmitted frames
Total amount of transmitted Modbus responses.
Transmitted Exc
Total amount of exception responses 1 and 2.
A
These exception responses usually reveal configuration errors on the
Modbus client's side.
Transmitted Exc
Total amount of exception responses 3.
B
These exceptions reveal the application level rejections.
TCP connection status
Shows the value "Green" via LED on WHMI, if TCP/IP instance is in use.
A Modbus client has connected to the TCP socket and Modbus TCP
messages are received regularly. In all other cases, it shows the value "Red"
via a LED.
The counters and status are reset when the client makes a TCP socket disconnection
or if the live TCP socket connection times out.

Common Modbus TCP/IP diagnostic counters

Table 116:
TCP/IP diagnostic counters (client independent)
Counter
Description
CnReject No sockets
Amount of connection requests rejected due to unavailable TCP sockets
CnReject Not reg
Amount of connection requests rejected since the client is not registered

Supported Modbus function codes

Table 117:
Function codes supported by RIO600
Function code
Name
01
Read coil status
02
Read digital input status
03
Read holding registers
04
Read input registers
05
Force single coil
06
Preset single register
08 sub
Diagnostics: Request query
function code
data
00
Description
Reads the status of discrete outputs
Reads the status of discrete inputs
Reads the contents of output registers
Reads the contents of input registers
Sets the status of a discrete output
Sets the value of a holding register
The data in the query data field is returned (looped
back) in the response. The entire response is
identical to the query.
Installation and Commissioning Manual
1MRS757488 H
RIO600