ABB Remote I/O RIO600 Installation And Commissioning Manual page 287

Table of Contents

Advertisement

1MRS757488 H
Table 182:
Behavior during IRF in RTD4 module
Module IRF
Behavior in an IRF condition
RIO600 as a whole
IRF in RTD4 module
Table 183:
Behavior during IRF in AOM4 module
Module IRF
Behavior in an IRF condition
RIO600 as a whole
IRF in AOM4 module
RIO600
Installation and Commissioning Manual
LECM
Continues normal
1.
function with corrective
action
2.
3.
4.
5.
LECM
Continues normal
1.
function with corrective
action
2.
3.
4.
5.
RTD4
Show IRF to user
Normal functionality is
by steady IRF LED
compromised
on LECM module
The RTD Module
under fault's
channel values as
reported over
GOOSE are forced
to "0"
Show IRF on WHMI
under Faults page
GOOSE: Updates
quality of all
modules' data
attributes and
RIO600 module
health as per IEC
61850
Opens DOM IRF
output contact, if it
is configured
AOM4
Show IRF to user
Normal functionality is
by steady IRF LED
compromised
on LECM module
Shows IRF source
information on
WHMI under Faults
page
AOM4 module
under fault's
channels are forced
to default, that is,
"0" and the AOM
module's channel's
physical status is
forced to "0"
GOOSE: Updates
quality of all
module's data
attributes and
RIO600 module
health as per IEC
61850
Opens DOM4 IRF
output contact, if it
is configured
Section 9
Troubleshooting
DIM8L/DIM8H, DOM4,
AOM4
1.
Continues normal
operation
2.
Shows error in
previous module
over LECM WHMI
(if detected)
DIM8L/DIM8H, DOM4,
RTD4
1.
Continues normal
operation
2.
Shows error in
previous module
over LECM WHMI
(if detected)
279

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents