1MRS757488 H
7.1.26
RIO600
Installation and Commissioning Manual
If any of the time element has not been updated, the time synch warning is turned
on and the time synch status in WHMI indicates "Bad".
If the value written in a time element is out of the acceptable value range for the
corresponding time element, the particular time element's value is not updated
and an exception code 4 is sent to the Modbus client.
If the Modbus master/client disconnects from RIO600, a time sync warning is
raised again in LECM and the time sync status in WHMI indicates "Bad".
If Modbus time sync command has not been received from the Modbus master/
client for a minimum time period of half an hour, a time sync warning is raised
again in LECM and the time sync status in WHMI indicates "Bad".
Table 121:
Time synchronization in RIO600
Modbus
Attribute name
address
(in decimal)
8
Time synchronisation
9
Time synchronisation
10
Time synchronisation
11
Time synchronisation
12
Time synchronisation
13
Time synchronisation

Parameter settings

Modbus communication needs to be enabled via the PCM600 path Configuration/
Station communication/MODBUS. The station communication parameters need to
be set to use Modbus communication in RIO600.
Table 122:
Station communication parameters for Modbus
Parameter name
Range
Modbus operation
ON/OFF
Modbus connection
1...100
timeout
TCP Client Modbus
ON/OFF
operation
Slave ID
1...254
Client IP
-
Binary input read
Latched
method
-
Instantaneo
us
Table continues on next page
Modbus TCP communication
Information Scale factor Data type
Year
1
Month
1
Day
1
Hour
1
Minute
1
Seconds
1
Unit
Default value
Description
-
Off
Select "ON" to enable Modbus
communication with client.
Sec
10
If there is no request from other client
within this timeout, RIO600 closes
the TCP connection.
-
Off
Select "ON" to enable Modbus
communication with the client.
-
-
Slave ID of RIO600
-
000.000.000
IP address of the Modbus client
.000
-
Latched
Binary input signal information is
stored until a Modbus request
command is received.
-
-
The current binary signal information
would be provided to the client upon
request.
Section 7
More
information
(Valid range)
Unsigned 16
2000...9999
Unsigned 16
1...12
Unsigned 16
1...31
Unsigned 16
0...23
Unsigned 16
0...59
Unsigned 16
0...59
179