1MRS757488 H
7.1.26
RIO600
Installation and Commissioning Manual
•
If any of the time element has not been updated, the time synch warning is turned
on and the time synch status in WHMI indicates "Bad".
•
If the value written in a time element is out of the acceptable value range for the
corresponding time element, the particular time element's value is not updated
and an exception code 4 is sent to the Modbus client.
•
If the Modbus master/client disconnects from RIO600, a time sync warning is
raised again in LECM and the time sync status in WHMI indicates "Bad".
•
If Modbus time sync command has not been received from the Modbus master/
client for a minimum time period of half an hour, a time sync warning is raised
again in LECM and the time sync status in WHMI indicates "Bad".
Table 121:
Time synchronization in RIO600
Modbus
Attribute name
address
(in decimal)
8
Time synchronisation
9
Time synchronisation
10
Time synchronisation
11
Time synchronisation
12
Time synchronisation
13
Time synchronisation
Parameter settings
Modbus communication needs to be enabled via the PCM600 path Configuration/
Station communication/MODBUS. The station communication parameters need to
be set to use Modbus communication in RIO600.
Table 122:
Station communication parameters for Modbus
Parameter name
Range
Modbus operation
ON/OFF
Modbus connection
1...100
timeout
TCP Client Modbus
ON/OFF
operation
Slave ID
1...254
Client IP
-
Binary input read
Latched
method
-
Instantaneo
us
Table continues on next page
Modbus TCP communication
Information Scale factor Data type
Year
1
Month
1
Day
1
Hour
1
Minute
1
Seconds
1
Unit
Default value
Description
-
Off
Select "ON" to enable Modbus
communication with client.
Sec
10
If there is no request from other client
within this timeout, RIO600 closes
the TCP connection.
-
Off
Select "ON" to enable Modbus
communication with the client.
-
-
Slave ID of RIO600
-
000.000.000
IP address of the Modbus client
.000
-
Latched
Binary input signal information is
stored until a Modbus request
command is received.
-
-
The current binary signal information
would be provided to the client upon
request.
Section 7
More
information
(Valid range)
Unsigned 16
2000...9999
Unsigned 16
1...12
Unsigned 16
1...31
Unsigned 16
0...23
Unsigned 16
0...59
Unsigned 16
0...59
179