Supervision Data - ABB Remote I/O RIO600 Installation And Commissioning Manual

Table of Contents

Advertisement

Section 7
Modbus TCP communication
Bit A
Reg A
2798
1586.14
2799
1586.15
2800
1587.00
2801
1587.01
1) Applicable (read and write) data attributes are mentioned under their respective data objects.
LD0.SCMLGGIO/LD0.SCMHGGIO
- .SPCSO1.stVal
- .SPCSO2.stVal
- .SPCSO3.stVal
- .SPCSO4.stVal
LD0.SCMLPGGIO/LD0.SCMHPGGIO
- CLOSE_ES
- OPEN_ES
- CLOSE_DS
- OPEN_DS
LD0.SCMLDGGIO/LD0.SCMHDGGIO
- CLOSE_DS
- OPEN_DS
LD0.SCMLEGGIO/LD0.SCMHEGGIO
- CLOSE_ES
- OPEN_ES
LD0.SCMLCGGIO/LD0.SCMHCGGIO
- OPEN_CB
- CLOSE_CB
7.2.46
Table 172:

Supervision data

Reg A
Type
Scale
2260
Unsigne
1
d 16
2261
Unsigne
1
d 16
2262
Unsigne
1
d 16
2263
Unsigne
1
d 16
2264
Unsigne
1
d 16
2265
Unsigne
1
d 16
:
:
:
2281
Unsigne
1
d 16
Table continues on next page
258
IEC 61850 name
SA name
<reserved>
OPEN_CB
CLOSE_CB
<reserved>
Supervision data
Supervision data register addresses provide information about the file revision and
checksum of RIO600's configuration and IO parameter file. It also provides
information about the firmware version (major, minor and patch) and its checksum of
the modules present in the RIO600.
IEC 61850 name
Description
<reserved>
Circuit Breaker Open
Command
Circuit breaker Close
Command
<reserved>
SA name
Description
RIO Configuration File
Revision
RIO Configuration File
Checksum
Reserved For Future Use
IO Parameters File Revision
IO Parameters File Checksum
Reserved For Future Use
:
Reserved For Future Use
1MRS757488 H
Values
0/1 = Off/On
0/1 = Off/On
Values
0...65535
0...65535
0
0...65535
0...65535
0
:
0
Installation and Commissioning Manual
RIO600