ABB Remote I/O RIO600 Installation And Commissioning Manual page 264

Table of Contents

Advertisement

Section 7
Modbus TCP communication
Bit A
Reg A
2702
1580.14
2703
1580.15
2704
1581.00
2705
1581.01
2720
1582.00
2721
1582.01
2722
1582.02
2723
1582.03
2724
1582.04
2725
1582.05
2726
1582.06
2727
1582.07
2728
1582.08
2729
1582.09
2730
1582.10
2731
1582.11
2732
1582.12
2733
1582.13
2734
1582.14
2735
1582.15
2736
1583.00
2737
1583.01
2752
1584.00
Table continues on next page
256
IEC 61850 name
SA name
<reserved>
OPEN_CB
CLOSE_CB
<reserved>
1)
1. LD0.SCMLGGIO8/
LD0.SCMHGGIO8
2. LD0.SCMLPGGIO8/
LD0.SCMHPGGIO8
3. LD0.SCMLDGGIO8/
LD0.SCMHDGGIO8
4. LD0.SCMLEGGIO8/
LD0.SCMHEGGIO8
5. LD0.SCMLCGGIO8/
LD0.SCMHCGGIO8
.SPCSO1.stVal
.SPCSO2.stVal
.SPCSO3.stVal
.SPCSO4.stVal
<reserved>
<reserved>
<reserved>
<reserved>
CLOSE_ES
OPEN_ES
CLOSE_DS
OPEN_DS
<reserved>
<reserved>
<reserved>
OPEN_CB
CLOSE_CB
<reserved>
1)
1. LD0.SCMLGGIO9/
LD0.SCMHGGIO9
2. LD0.SCMLPGGIO9/
LD0.SCMHPGGIO9
3. LD0.SCMLDGGIO9/
LD0.SCMHDGGIO9
4. LD0.SCMLEGGIO9/
LD0.SCMHEGGIO9
5. LD0.SCMLCGGIO9/
LD0.SCMHCGGIO9
.SPCSO1.stVal
Description
<reserved>
Circuit Breaker Open
Command
Circuit breaker Close
Command
<reserved>
SCM-8
Digital Output Channel 1
Digital Output Channel 2
Digital Output Channel 3
Digital Output Channel 4
<reserved>
<reserved>
<reserved>
<reserved>
Earth Switch Close Command
Earth Switch Open Command
Disconnector Close Command
Disconnector Open Command
<reserved>
<reserved>
<reserved>
Circuit Breaker Open
Command
Circuit breaker Close
Command
<reserved>
SCM-9
Digital Output Channel 1
Installation and Commissioning Manual
1MRS757488 H
Values
0/1 = Off/On
0/1 = Off/On
0/1 = Off/On
0/1 = Off/On
0/1 = Off/On
0/1 = Off/On
0/1 = Off/On
0/1 = Off/On
0/1 = Off/On
0/1 = Off/On
0/1 = Off/On
0/1 = Off/On
0/1 = Off/On
RIO600