Connecting Binary Output Signals - ABB Remote I/O RIO600 Installation And Commissioning Manual

Table of Contents

Advertisement

Section 5
Installing
5.2.4
38

Connecting binary output signals

Check that the proper power supply and LECM modules are mounted on the DIN rail.
The DOM4 module has four signaling outputs with a common return for a pair of two
outputs. The default contact status during auxiliary shutdown and startup phase is
"Opened". Once a valid configuration is accepted, the contacts operate based on the
output activation commands received via communication services.
The rated voltage for binary output connection is 250 V AC or 250 V DC. The binary
output contact operation time is 5...7 ms.
1.
Fasten the output connector through the upper and lower screw terminals.
2.
Connect wires to the DO and COM signals.
DOM4
DO1
DO2
DO3
DO4
GUID-1E9D25F1-9224-4DBB-921A-F310E2ACAE7A V2 EN
Figure 18:
DOM4 terminals
Table 10:
Screw terminal of the DOM4 connection
X1
1
2
3
Table continues on next page
X1
COM
1
DO1
2
DO2
3
DO3
4
DO4
5
COM
6
Binary output terminal Description
COM
Isolated output pair 1
DO1
DO2
1MRS757488 H
LED
DO1
DO2
Installation and Commissioning Manual
RIO600