1MRS757488 H
RIO600
Installation and Commissioning Manual
Description
Pulsed magnetic field
Conducted disturbance induced
by radio frequency fields,
Amplitude modulated
Fast low-energy transient (EFT)
(including functional earth port)
Damped oscillatory waves
(HFD) 100 kHz and 1 MHz burst
Power supply and input/
output ports
Communication port
Slow high-energy transient
(surge1.2/50 μs voltage pulse)
Auxiliary power supply and
1)
input/output ports
Communication port
Voltage dips, short interruptions
and voltage variation immunity
tests (AC 50 Hz and 60 Hz)
Voltage dips, supply interruption
and voltage variations on DC
input power port (immunity
tests)
Ripple voltage
Gradual shut-down/start-up test
(for DC power supply)
Ramp towards shut-down
Wait at power of condition
Ramp towards start-up
Power frequency voltage 50 Hz
and 60 Hz
Input/output port
Table continues on next page
Device and functionality tests
Type test value
1000 A/m; 6.4/16 μs Tr/Td; 5
pulses positive/negative; 10 s
(time interval)
0.15...80 MHz - 10 V (unmod,
RMS); 80% AM (1 kHz); 150 Ω
source impedance
27 and 68 MHz (spot
frequencies); 10 V (unmod,
RMS); 80% AM (1 kHz); 150 Ω
source impedance
5/50 ns Tr/Td; 5 kHz repetition
frequency
4 kV (peak) for power supply
input/output ports and 2 kV
(peak) for communication port
100 kHz and 1 MHz frequency;
75 ns Tr; 40 Hz and 400 Hz
repetition frequency; 200 Ω
source impedance
Differential mode: 1 kV (peak)
Common mode: 2.5 kV (peak)
Differential mode: not applicable
Common mode: 1 kV (peak)
1.2/50 μs Tr/Th (open circuit)
8/20 μs Tr/Th (short circuit)
±4 kVp (L-Gnd) ±2 kVp (L-L)
±2 kVp (L-Gnd) while no L-L test
is applicable
30% reduction for 25/30 cycles
60% reduction for 10/12 cycles
100% reduction for 0.5, 1.0, 2.5
and 5.0 cycles
100% reduction for 250/300
cycles
30% reduction for 500 ms
60% reduction for 200 ms
100% reduction for 10, 20, 30
and 50 ms
100% reduction for 5 s
15% U
frequencies of ripple
n
100/120 Hz (for 50/60 Hz)
60 s
5 min
60 s
Section 11
Reference
IEC 61000-4-9, Level 5
IEC 60255-26 and IEC
61000-4-6, Level 3
IEC 60255-26 and IEC
61000-4-4
IEC 60255-26 and IEC
61000-4-18
IEC 60255-26 and IEC
61000-4-5
IEC 60255-26 and IEC
61000-4-11
IEC 60255-26 and IEC
61000-4-29
IEC 60255-26, IEC 61000-4-17
and IEEE C37.90-2005
IEC 60255-26
IEC 60255-26 and IEC
61000-4-16