Behavior During Irf Condition - ABB Remote I/O RIO600 Installation And Commissioning Manual

Table of Contents

Advertisement

1MRS757488 H
9.1.1
Table 179:
Behavior during IRF in LECM module
Module IRF
IRF in LECM module
RIO600
Installation and Commissioning Manual
LED
Color
IRF
Red
DI1 to DI4
Yellow
HS1 to HS4
DI1 to DI4
Yellow
HS1 to HS4

Behavior during IRF condition

Behavior in an IRF condition
RIO600 as a whole
Normal functionality is
compromised
State
ON
ON
OFF
LECM
1.
Shows error by steady red
LED on LECM module
2.
Shows IRF source
information on WHMI
under faults page
3.
Force all DOM4 outputs to
default, that is, "0"
4.
All AOM4 output continues
to drive the last GOOSE
received value
5.
GOOSE: Update Quality of
all data attributes and
RIO600 module health as
per IEC 61850
6.
Open DOM4 IRF output
contact, if configured
Section 9
Troubleshooting
Description
Module is in error
condition
Binary I/O signal
activated
Binary I/O signal not
activated
DIM8L/DIM8H, DOM4, AOM4,
RTD4
1.
Continues normal
operation
2.
Shows error in previous
module over LECM WHMI
(if detected)
277