Section 6
Commissioning
Table 104:
Operation parameters for three-position earthing switch, two-position earthing switch, two-position disconnector switch or
circuit breaker control application
Parameter name
Motor Parameters
Motor start time out
Motor braking
Motor U
nominal
Motor(s) duty cycle
Earthing switch
parameters
Earthing switch close
time-out
Earthing switch open
time-out
Disconnector parameters
Disconnector close time-
out
Disconnector open time-
out
CB parameters
Trip coil pulse time
Closing coil pulse time
Input channels
Debounce Time (Filter
time)
Oscillation Upper Limit
Oscillation Suppression
Hysteresis
Table continues on next page
160
Range
Unit
0...32000
ms
Not used/used
24...250
VDC
1...100
%
0...32000
ms
0...32000
ms
0...32000
ms
0...32000
ms
1...500
ms
1...500
ms
5...4095
ms
2...63
Counts
1...62
Counts
Default value
Description
0
Maximum time from
Starting motor to
definitely leave defined
Start position
Not used
Motor braking
110
Motor nominal voltage
100
Duty cycle to run motor(s)
25000
Maximum time from
Earthing switch opened
to Earthing switch closed
25000
Max time from Earthing
switch closed to Earthing
switch opened
25000
Maximal time from
Disconnector opened to
Disconnector closed
25000
Maximal time from
Disconnector closed to
Disconnector opened
100
Pulse time for trip coil
Pulse ends if start
position leaved or end
position reached
100
Pulse time for closing coil
Pulse ends if start
position leaved or end
position reached
10
This parameter is the
debounce time for the
input signal in ms.
63
This parameter is the
oscillation suppression
upper limit.
The parameter value acts
as the count for upper
limit.
62
This parameter is the
oscillation suppression
hysteresis.
The parameter value acts
as the count for
hysteresis.
Installation and Commissioning Manual