Connecting Rtd/Ma Signals - ABB Remote I/O RIO600 Installation And Commissioning Manual

Table of Contents

Advertisement

1MRS757488 H
5.2.5
RIO600
Installation and Commissioning Manual
X1
4
5
6

Connecting RTD/mA signals

Use a shielded cable for the connection of RTD/mA signals. Connect the shield of the
cable to the DIN rail through an earthing clamp, for example, Weidmuller Earthing
Clamp: 1252520000 (KLBUE 4-13.5 FM4).
Check that the proper power supply and LECM modules are mounted on the DIN rail.
The RTD4 module has two sets of connectors where each set accepts two RTD/mA
signals.
1.
Fasten the input connector through the upper and lower screw terminals.
2.
Connect the signals based on the type of configuration.
For 2-wire RTD configuration, connect the RTD signals between - and +
terminals and short - and C terminals, else there will be an IRF.
RTD4
RTD1
RTD2
RTD3
RTD4
GUID-6B99373F-69D2-490B-8563-BB772E0018B1 V2 EN
Figure 19:
For 3-wire RTD configuration, connect the three terminals of RTD sensor
between C, - and + terminals.
Binary output terminal Description
DO3
Isolated output pair 2
DO4
COM
X1
1C
1
1-
2
1+
3
2C
4
2-
5
2+
6
X2
3C
1
3-
2
3+
3
4C
4
4-
5
4+
6
Earth Clamp (mounted on DIN Rail)
2-wire RTD
Section 5
Installing
LED
DO3
DO4
Resistor sensor
Resistor sensor
Resistor sensor
Resistor sensor
39