ABB Remote I/O RIO600 Installation And Commissioning Manual page 294

Table of Contents

Advertisement

Section 10
Technical data
286
Description
Maximum interruption time in
the auxiliary DC without
resetting the RIO600 modules
Ripple in the DC auxiliary
voltage
Reversal of DC power supply
polarity
Burden of auxiliary voltage
supply
Quiescent (Pq) condition
(none of the 20 I/O
channels are activated)
Operating condition (20
binary output channels in
DOM4 modules are
activated)
Module configuration
PSM + LECM + DIM8H
PSM + LECM + DIM8L
PSM + LECM + DOM4
PSM + LECM + DOM4 (5)
PSM (2) + LECM + DIM8H (5)
PSM (2) + LECM + DIM8L (5)
PSM (2) + LECM + DOM4 (10)
Table 191:
Binary inputs
Description
Rated voltage
Operating voltage range
Current drain
Power consumption/input
channel
Threshold voltage
Reaction time
Table 192:
Signal outputs (digital output module DOM4)
Description
Operating time
Nominal coil power
Rated voltage
Continuous contact carry
Table continues on next page
PSMH
100 ms at U
nominal
aux
Max. 15% of the DC value (at frequency of 100 Hz)
1 minute for each polarity
<4.0 W nominal
<12.0 W (maximum)
Condition
All DIs activated
All DOs activated
All DOs activated
All DIs activated
All DOs activated
DIM8H
110...250 V DC
±20% of rated voltage
3...3.7 mA
330...925 mW
78 V DC
5 ms...4.0 s filtering time
Value
<5 ms
<500 mW
250 V AC/DC
5 A
Installation and Commissioning Manual
1MRS757488 H
PSML
50 ms at U
nominal
aux
Max. consumption for PSMH
and PSML
2 W
4 W
12 W
11 W
22 W
DIM8L
24, 30, 48, 60 V DC
±20% of rated voltage
2 mA
30...130 mW
13 V DC
5 ms...4.0 s filtering time
RIO600