Section 6
Commissioning
Table 110:
TCSHSCBR/TCSLSCBR settings
Name
Values (Range)
Off
Operation
On
Operate Delay Time
20...300000
Reset Delay Time
0...60000
166
TCS status
(input 4)
GUID-4E6CD401-5CA9-4801-8AFA-90F3EBEC2E9B V1 EN
Figure 88:
Functional module diagram
TCS status
This module receives the trip circuit status from binary input 4. A detected failure in
trip circuit activates the timer.
Timer
Once activated, the timer runs until the set value of Operate Delay Time has elapsed.
The time characteristic is according to DT. When the operation timer has reached the
maximum time value, the TCSLSCBR_ALR output is activated. If a drop-off situation
occurs during the operate time up counting, the reset timer is activated. If the reset
timer reaches the value set by Reset Delay Time, the operation timer resets and the
TCSLSCBR_ALR output is deactivated.
TCSHSCBR is available for high-voltage circuit breaker and
TCSLSCBR for low-voltage circuit breaker configuration
Signals
Table 108:
TCSHSCBR Output signals
Name
TCSHSCBR_ALR
Table 109:
TCSLSCBR Output signals
Name
TCSLSCBR_ALR
Settings
Unit
-
ms
ms
Timer
t
Type
Boolean
Type
Boolean
Step
Default
-
On
1
20
1
1000
1MRS757488 H
TCSLSCBR_ALR
Description
Alarm output
Description
Alarm output
Description
Operation Off / On
Operate delay time
Reset Delay Time
Installation and Commissioning Manual
RIO600