Connecting Wires; Connecting Power Supply - ABB Remote I/O RIO600 Installation And Commissioning Manual

Table of Contents

Advertisement

1MRS757488 H
5.2
5.2.1
RIO600
Installation and Commissioning Manual
RIO600
Ready
Ready
Ready
IRF
IRF
LF Fwd / Rv
THD / TDD
Non Dir OC
OC Fwd / Rv
Rx/Tx
Non Dir EF
10M/100M
EF Fwd / Rv
Volt Presence
SIM8F
PSMH
LECM
GUID-749F7169-F4AD-4F30-B0E9-D535AEDB410C V3 EN
Figure 14:
RIO600 configuration: 1 × SIM8F + 1 × SIM4F + 1 × DIM8H + 1 ×
DOM4

Connecting wires

Connecting power supply

RIO600 supports power supply modules PSMH and PSML.
With the PSMH module, the voltage range for the external power connection is
110...250 V DC (±20%) and 100...240 V AC (-15% to +10%).
With the PSML module, the voltage range for the external power connection is U
nominal 24, 30, 48, 60 V DC (with variation of 50...120% of Un) and the startup
threshold is 19.2 V DC (24 V DC * 80%).
1.
Fasten the power connector through the upper and lower screw terminals.
2.
Connect the power supply cable to the power supply module.
Ready
Ready
Ready
IRF
IRF
IRF
DI1
DO1
Inrush
DI2
DO2
Fault Pass
DI3
DO3
Non Dir OC
Neg Seq OC
DI4
DO4
Non Dir EF
DI5
DI6
DI7
DI8
DIM8H
SIM4F
DOM4
Section 5
Installing
aux
33