Section 6
Commissioning
162
Table 105:
Interlocking rules for motor driven switches
Operation
Close earthing switch
Close disconnector
Input status
Interlocking rules for circuit breaker control
Smart control module configured for a circuit breaker application controls two double
poled coils. The circuit breaker interlocking has to be realized inside the belonging
protection and control device.
Table 106:
Interlocking rules for circuit breaker control
Operation
CB Open
CB Close
Irrespective of the circuit breaker's current position, if a command
comes to an open circuit breaker, it will be always executed.
Binary input debounce time (filter time)
The filter time eliminates debounces and short disturbances on a binary input. The
filter time is set for each binary input.
Position of switch
If Earthing switch is between
OPEN and CLOSE positions
(intermediate position) and the
disconnector is in OPEN
position
If Disconnector is between
OPEN and CLOSE positions
(intermediate position) and the
earthing switch is in OPEN
position
Earthing switch is in OPEN
position and disconnector is in
OPEN position
Disconnector is in OPEN
position and earthing switch is in
OPEN position
Unexpected (wrong) position
indication
Position of switch
Circuit breaker ready
Circuit breaker close
Installation and Commissioning Manual
1MRS757488 H
Command allowed
Open earthing switch
Open disconnector
Allowed to CLOSE
Allowed to CLOSE
Stop motor immediately
Allowed state
Close circuit breaker
No action
RIO600