1MRS757488 H
3.4.1
3.5
RIO600
Installation and Commissioning Manual
Support for IEC 61850 Edition 1 and Edition 2 enabling the creation of IED
objects in PCM600 with the selected protocol standard version
Exporting configuration files to a local machine
Establishing GOOSE communication between the devices configured in
PCM600 using IEC 61850 Configuration or Goose Engineering through
Application Configuration or both

PCM600 and RIO600 connectivity package version

Protection and Control IED Manager PCM600 Ver.2.9 Hotfix 2 or later
RIO600 Connectivity Package Ver.1.8 or later

Communication

RIO600 supports horizontal Generic Object Oriented Substation Event (GOOSE)
communication according to the IEC 61850 substation automation standard versions
Edition 1 and Edition 2. It meets the horizontal communication performance criteria
for protection and fault detection defined by IEC 61850-5, that is, peer-to-peer
communication <10 ms. Currently, the IEC 61850 MMS profile for vertical TCP/IP
communication is not supported.
Modbus TCP communication to one Modbus TCP client is also supported. IEC 61850
GOOSE and Modbus TCP can be used in parallel in the same Ethernet-based station
bus.
RIO600 sends and receives binary and analog signals to or from the ABB Relion
series protection relays and the COM600 station automation unit/RTU using the IEC
61850-8-1 GOOSE profile or Modbus TCP. Any RTU supporting these protocols can
be used. RIO600 subscribes to a GOOSE message from up to five peer protection
relays and publishes to multiple protection relays as configured. Up to seven GOOSE
data sets can be published. It is possible to send time-stamped events using the
GOOSE service with a T0 class accuracy.
RIO600 also supports Modbus TCP communication used in Ethernet networks. The
communication type is client-server where RIO600 acts as a Modbus TCP server.
RIO600 Modbus TCP server supports connection to one Modbus TCP client.
RIO600 communication module includes a galvanic RJ-45 port with 10/100 Mbits/s
or fiber-optic LC Ethernet for IEC 61850 GOOSE and Modbus TCP communication.
The used cable must be a shielded twisted pair cable CAT5e at the minimum or a
multimode fiber-optic cable with an LC connector.
Using the same Ethernet port, RIO600 can be connected in parallel to PCM600 and a
Web browser over the same communication bus.
Section 3
RIO600 overview
®
21