Negative-Sequence Overcurrent Indication Nsptoc - ABB Remote I/O RIO600 Installation And Commissioning Manual

Table of Contents

Advertisement

1MRS757488 H
Table 82:
PHSVPR Settings
Name
Values (Range)
Operation
Off
On
Alive Phase
1 out of 3
Supervision
2 out of 3
3 out of 3
Dead Phase
1 out of 3
Supervision
2 out of 3
3 out of 3
Voltage Live Value
300...25000
Voltage Dead Value
300...25000
6.1.6.7
RIO600
Installation and Commissioning Manual
Signals
Table 81:
PHSVPR Output signals
Name
PHSVPR_ULive
PHSVPR_UDead
Settings
Unit
-
-
-
V
V
Table 83:
PHSVPR Technical data
Characteristic
Operation accuracy

Negative-sequence overcurrent indication NSPTOC

Identification
Description
Negative-sequence overcurrent
protection
Functionality
The negative-sequence overcurrent protection function NSPTOC is used to increase
sensitivity to detect single-phase and phase-to-phase faults or unbalanced loads due
to, for example, broken conductors or unsymmetrical feeder voltages.
Type
Boolean
Boolean
Step
Default
-
On
-
1 out of 3
-
3 out of 3
1
6000
1
300
Value
At frequency f = f
±5% in the range of 480 V...9.6 kV
±0.5% in the range of 9.6...28.8 kV
IEC 61850
IEC 60617
identification
identification
NSPTOC
Section 6
Commissioning
Description
Indicating voltage presence
Indicating voltage absence
Description
Operation Off/On
Number of phases
required for voltage
presence detection
Number of phases
required for voltage
absence detection
Limit for phase to
neutral voltage
presence detection
Limit for phase to
neutral voltage
absence detection
n
ANSI/IEEE C37.2
device number
I2>
46
137