Operating Parameter Settings Dom4 - ABB Remote I/O RIO600 Installation And Commissioning Manual

Table of Contents

Advertisement

1MRS757488 H
6.1.3
Table 22:
Operating parameter settings for DOM4
Parameter name
Range
Description
Pulse Length
Signal Type
Output Channel 1
Inversion
Output Channel 2
Inversion
Output Channel 3
Inversion
Output Channel 4
Inversion
Output Channel 1
Enabled
Output Channel 2
Enabled
Output Channel 3
Enabled
Output Channel 4
Enabled
RIO600
Installation and Commissioning Manual
The binary input is regarded as non-oscillating if the number of valid state changes
during configured time period is less than the set oscillation level value minus the set
oscillation hysteresis value. The oscillation hysteresis must be set lower than the
oscillation level to enable the input to be restored from oscillation. When the input
returns to a non-oscillating state, the binary input is deblocked (the status is valid) and
an event is generated.

Operating parameter settings DOM4

Unit
10 to 65535
ms
Static/Pulse
Non-Inverted/Inverted
Non-Inverted/Inverted
Non-Inverted/Inverted
Non-Inverted/Inverted
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Table 23:
Details of output channels on a DOM4 board configured for IRF
Status
Power-on
Normal operating condition
IRF condition
It is possible to map IRF condition to any binary output via Signal
Matrix in PCM600.
Default value
Description
Digital Output
User defined channel name not exceeding 30
1...4
characters
10
The integer value in this parameter indicates the
pulse length for the output channels in
milliseconds (ms). This parameter is configurable
separately for each output channel.
Static
output signal type: static/pulse
This parameter is configurable separately for
each output channel.
Non Inverted
channel 1 output type: non-inverted/inverted
Non Inverted
channel 2 output type: non-inverted/inverted
Non Inverted
channel 3 output type: non-inverted/inverted
Non Inverted
channel 4 output type: non-inverted/inverted
Enabled
channel 1: enabled/disabled
Enabled
channel 2: enabled/disabled
Enabled
channel 3: enabled/disabled
Enabled
channel 4: enabled/disabled
Contact condition
Open
Closed
Open
Section 6
Commissioning
LED status
OFF
ON
OFF
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents