Figure 73:
Illustration of amplitude and resistive current sectors when
directional mode is set to "Forward" and setting operating quantity =
"Resistive"
The resistive mode is valid for resonant earthed networks and high-resistance earthed
systems, but not in case of unearthed networks. The resistive mode must be selected
when there is a risk of local overcompensation of a protected feeder, that is, when the
earth-fault current is compensated with distributed compensation coil and their
inductive current exceeds the amount of capacitive current produced by the phase-to-
earth capacitance of the feeder.
In compensated networks, where distributed compensation coils are
also used to compensate earth-fault current, setting Operating
Quantity should be set to "Resistive". This enables secure and
dependable directional determination also in case of local
overcompensation where the earth-fault current produced by the
healthy feeder can become inductive.