ABB Remote I/O RIO600 Installation And Commissioning Manual page 124

Table of Contents

Advertisement

Section 6
Commissioning
Table 75:
DEFPTOC Settings
Name
Values (Range)
Operation
Off
On
Start Value
4...200
200...1000
Voltage Start Value
500..1000
Operate Delay Time
40...60000
Enable Voltage Limit
No
Yes
Directional Mode
Forward
Reverse
Non Directional
Operation Mode
Phase angle
IoSin
IoCos
Characteristics
-179...180
Angle
Max Forward Angle
0...180
Max Reverse Angle
0...180
Min Forward Angle
0...180
Min Reverse Angle
0...180
Min Operate Current
-
Min Operate Voltage
-
Abs Hyst Oper Qty
0.0...50.0
Abs Hyst Pol Qty
0...2500
116
Settings
Unit
-
A
A
V
ms
-
-
-
Deg
Deg
Deg
Deg
Deg
A
V
A
V
Step
Default
-
On
1
4
5
1
500
10
80
-
Yes
-
Forward
-
Phase angle
1
0
1
80
1
80
1
80
1
80
-
1
-
500
0.1
0.1
0.1
200
1MRS757488 H
Description
Operation Off/On
Start value for earth-
fault detection
Voltage start value
Operate delay time
Additional check for
voltage before
issuing trip
Directional mode
Operation criteria
Characteristics
angle
Maximum phase
angle in forward
direction
Maximum phase
angle in reverse
direction
Minimum phase
angle in forward
direction
Minimum phase
angle in reverse
direction
Minimum operating
current to allow
directional criteria
Minimum operating
voltage to allow
directional criteria
Absolute hysteresis
for operating
quantity
Absolute hysteresis
for polarizing
quantity
Installation and Commissioning Manual
RIO600