ABB Remote I/O RIO600 Installation And Commissioning Manual page 284

Table of Contents

Advertisement

Section 9
Troubleshooting
276
LED
Color
Non Dir Oc
Green
Non Dir Oc
Green
Neg Seq Oc
Green
Neg Seq Oc
Green
Non Dir EF
Green
Non Dir EF
Green
The binary input LED is ON if the input signal is HIGH (DIM8H:
~100 V DC, DIM8L: ~24 V DC) and OFF if the signal is LOW (~0 V
DC). The operation is independent of normal/inverted parameter.
The binary output LED is ON if the output contact is closed and OFF
if the output contact is open. The operation is independent of normal/
inverted parameter.
Flashing protection indication LEDs signify that the fault has been
cleared and is waiting for reset according to the Fault indication reset
method setting.
Table 178:
LED indicators (SCM module)
LED
Color
Ready
Green
Ready
Green
IRF
Red
Table continues on next page
State
Description
OFF
Non-directional
overcurrent fault
detection condition is
not detected
ON
Non-directional
overcurrent fault
detection condition is
detected
OFF
Negative-sequence
overcurrent fault
condition is not
detected
ON
Negative-sequence
overcurrent fault
condition is detected
OFF
Non-directional earth-
fault detection
condition is not
detected
ON
Non-directional earth-
fault detection
condition is detected
State
Description
ON
Module is ready
Flashing
Module is powered on,
configuration is
pending
OFF
Module is healthy
Installation and Commissioning Manual
1MRS757488 H
RIO600

Hide quick links:

Advertisement

Table of Contents
loading