Local/Remote Mode; Time Synchronization - ABB Remote I/O RIO600 Installation And Commissioning Manual

Table of Contents

Advertisement

Section 6
Commissioning
6.4
6.5
168
For Analog Output Module (AOM4), in case of failsafe condition, the module
continues to drive the old value. In case of power-off condition, the module drives 0
mA current.

Local/Remote mode

RIO600 can be set to Local/Remote mode using any of the binary input signals,
GOOSE signal or through a Modbus command. The Local/Remote mode can be
instantiated using Signal Matrix tool. Different combinations are possible based on
the Local/Remote setting.
Table 113:
Local/Remote mode options
Local/
OR Logic
Remote
mode
-
NO
Remote
NO
Local
NO
-
YES
Remote
YES
Local
YES

Time synchronization

RIO600 can be synchronized to an NTP time server or the time synchronization can
be achieved using Modbus TCP client.
Time synchronization is used to synchronize the device's real time clock. Using time
synchronization, RIO600 can show the correct time in its WHMI and time stamp the
header and data events of GOOSE messages properly.
Time synchronization is not mandatory. The time stamp attribute is
not included by default in GOOSE data sets.
RIO600 does not support DST and therefore the used time is always
UTC in WHMI and events.
Local
Remote
Intermodule
Binary Goose
communicati
subscribing
on support
(commands
from DIM8)
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
NO
1MRS757488 H
Binary Goose
Binary
publishing
Modbus write
operations
YES
YES
YES
YES
YES
NO
YES
N/A
YES
N/A
YES
N/A
Installation and Commissioning Manual
Binary
Modbus read
operations
YES
YES
YES
N/A
N/A
N/A
RIO600