ABB Remote I/O RIO600 Installation And Commissioning Manual page 87

Table of Contents

Advertisement

1MRS757488 H
RIO600
Installation and Commissioning Manual
Signals
Table 43:
PEMMXU Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
U_A
SIGNAL
U_B
SIGNAL
U_C
SIGNAL
Table 44:
PEMMXU Output signals
Name
VA.phsA cVal
W.phsA cVal
VAr.phsA cVal
VA.phsB cVal
W.phsB cVal
VAr.phsB cVal
VA.phsC cVal
W.phsC cVal
VAr.phsC cVal
TotVA
TotW
TotVAr
TotPF
Hz
Table 45:
PEMMXU Technical data
Characteristic
Operation accuracy
Suppression of harmonics
Default
-
-
-
-
-
-
Type
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
Value
At frequency f = f
All three voltages are in the range of 9.6...14.4 kV
or 19.2...28.8 kV.
All three currents are in the range of 80...630 A.
Active power and energy are in the range |PF| >
0.71.
Reactive power and energy are in the range |PF| <
0.71.
±1.0% for active power P (±0.5% at +25ºC )
±3.0% for reactive Q and apparent power S (±1%
at +25ºC )
±0.03 for power factor
RMS: No suppression
Section 6
Commissioning
Description
Phase A current
Phase B current
Phase C current
Phase to earth voltage
A
Phase to earth voltage
B
Phase to earth voltage
C
Description
Apparent power Phase A
Active power Phase A
Reactive power Phase A
Apparent power Phase B
Active power Phase B
Reactive power Phase B
Apparent power Phase C
Active power Phase C
Reactive power Phase C
Total Apparent power
Total Active power
Total Reactive power
Total Power Factor
System frequency