ABB Remote I/O RIO600 Installation And Commissioning Manual page 99

Table of Contents

Advertisement

1MRS757488 H
Table 61:
PHPTOC Settings
Name
Values (Range)
Operation
Off
On
No. of Start Phases
1 out of 3
2 out of 3
3 out of 3
Start Value
50...2000
Operate Delay Time
40...60000
Absolute Hysteresis
0.0...100.0
RIO600
Installation and Commissioning Manual
The OP GENERAL output is available at LED 5 of the SIM8F module.
The phase segregated as well as general start and operate outputs STR GENERAL,
STR PHSA, STR PHSB, STR PHSC, OP GENERAL, OP PHSA, OP PHSB and OP
PHSC are available over communication.
Signals
Table 60:
PHPTOC Output signals
Name
Op general
Op phsA
Op phsB
Op phsC
Str general
Str phsA
Str phsB
Str phsC
Settings
Unit
-
-
A
ms
A
Table 62:
PHPTOC Technical data
Charateristic
Operation accuracy
Operate time accuracy (DMT)
Type
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Boolean
Step
Default
-
On
-
1 out of 3
10
480
10
40
0.1
3.0
Value
Depending on the frequency of the current
measured: f = f
±1.5% of the set value
±1.0% of the set value or ±20 ms
Section 6
Commissioning
Description
General operate signal
Operate signal for phase A
Operate signal for phase B
Operate signal for phase C
General start signal
Start signal for phase A
Start signal for phase B
Start signal for phase C
Description
Operation Off/On
Number of phases
required for operate
activation
Start value for
overcurrent fault
detection
Operate delay time
Absolute hysteresis
for current