Section 6
Commissioning
Parameter name
Range
IP SNTP Secondary
Physical MAC Address
Check
Physical MAC address
6.1.1.1
6.1.1.2
6.1.2
58
Unit
Disabled/Enabled

Standalone configuration

RIO600 can be configured to operate in a standalone mode. During this mode, RIO600
ignores all events from the publisher. It also does not check for any communication
errors or warnings and the modules can be configured as desired. With the parameter
default value "false", the Ethernet cable is expected to be connected, otherwise
RIO600 indicates a warning due to communication failure.

Intermodule communication

Binary signals in RIO600 can be configured to operate the outputs within the same
RIO600 stack. Any binary signal can be mapped to any of the output contacts. RIO600
supports the one-input NOT logic function and four-input OR and AND logic
functions through which signals can be passed and mapped to one output contact. A
logic output can also be available on GOOSE through the MVGAPC block. RIO600
supports up to two MVGAPC blocks, 20 OR, 20 AND, and 20 NOT logic blocks per
RIO600 stack.

Operating parameter settings DIM8H and DIM8L

The parameters for DIM8H and DIM8L are the same.
Default value
Description
192.168.2.165
IP address for SNTP server 2
If the second SNTP server is not required,
configure this field with the value "0.0.0.0" to
disable the server.
Disabled
Disabled = Physical MAC address check disabled
Enabled = Physical MAC address check enabled
If this parameter is enabled, then RIO600 checks
physical MAC address of the publisher IED and
will only accept GOOSE message subscribed by
RIO600.
In this way, RIO600 can do an additional security
verification of peer IED.
To be used with care as this parameter does not
update if the system configuration is updated or
peer IED is replaced.
00:00:00:00:00:
Physical MAC address of the publisher IED.
00