ABB Remote I/O RIO600 Installation And Commissioning Manual page 141

Table of Contents

Advertisement

1MRS757488 H
RIO600
Installation and Commissioning Manual
Uo
Io
GFC release
Operate
Delay Timer
Reset Delay
Timer
MFAPSDE_ST
MFAPSDE_Oper
Reset delay time
Start delay time
GUID-C9DD9B74-E46F-4FFB-A7C7-F022F9648430 V1 EN
Figure 76:
Operation of function
Timer
If the detected fault direction is opposite to the set directional mode and GFC release
is active, MFAPSDE_ReEF output is activated once Start delay time has elapsed.
Reset timer is activated at the falling edge of General Fault Criterion release, that is,
when zero-sequence voltage falls below Voltage start value. MFAPSDE_ReEF is
reset once the reset delay time elapses. MFAPSDE_ReEF is also available as a
GOOSE output. If the Power direction logic setting is set to "Enable", the active
power flow direction must be opposite to the set directional mode to activate
MFAPSDE_ReEF.
Operate delay time
Start delay time
Section 6
Commissioning
133