Calculating The Number Of Inputs/Outputs Type - Festo FB16 Electronic Manual

Valve terminal type 03/05, field bus connection
Table of Contents

Advertisement

VIFB16 - 03/05
Table for calculating the inputs/outputs of type 03
INPUTS
1. Number of 4-input modules
2. Number of 8-input modules
3. The 4 status bits are assigned internally
automatically by the terminal. They must be treated
like inputs and must be added to the intermediate sum:
Total sum of inputs (max. 64)
OUTPUTS
4. Number of S-type sub-base modules (type 03)
5. Number of D-type sub-base modules (type 03)
6. Check whether the sum of 4. + 5. can
be divided by 4 without remainder.
This check is necessary because of
the 4-bit orientated internal
addressing of the terminal.
Different cases:
a) If divisible by 4 without remainder:
continue with 7.
b) If not, round up (+ 2 outputs)
7. Number of electronic output modules
Total sum of outputs (max. 64)
Fig. 4/2: Calculating the number of inputs/outputs of type 03
4-8
4. Commissioning
Calculating the number of inputs/outputs
type 03
Copy the table for further calculations on the
number of inputs and outputs.
Intermediate total of 4. + 5.
______
4
+
______
8
+
=
______
2
+
______
4
=
+
+
______
4
=
Σ
I
Σ
I
4I
Σ
I
Σ
O
Σ
O
Σ
O
2O
Σ
O
Σ
O
0506b