Festo FB16 Electronic Manual page 68

Valve terminal type 03/05, field bus connection
Table of Contents

Advertisement

VIFB16 - 03/05
3-26
3. Installation
Connection example (type 05)
The following diagram shows the connection of a
common 24 V supply for pins 1 and 2. Please
note that:
the outputs/valves must be protected against
short circuit/overload with an external 10 A
fuse (slow blowing)
the supply to the electronic components and
inputs should be fused externally with 3.15 A
against short circuit/overload (recommenda-
tion)
that the operating voltage of the sensors is
separately fused (2 A)
that the operating voltage of the valves is
separately fused (4 A, slow blowing)
the common tolerance of DC 24 V ± 10 %
must be observed
the operating voltage supply to the node is
made via the adapter cable
equalizing currents must be avoided when
both earth cables are connected, e.g. by
means of cables with appropriate cross
section as a potential compensation.