4. Commissioning

Basic rule 1

With a mixed fitting, consideration is given to
the address assignment of the valves, digital I/O
modules and status bits.
1.
Outputs:
The address assignment of the outputs
does not depend on the inputs.
1.1 Address assignment of valves:
Addresses should be assigned in
ascending order without gaps.
Counting should begin on the node
from left to right.
S-type sub-base mod. always occupy 2 add.
D-type sub-base mod. always occupy 4 add.
ISO valve locations always occupy 2 add.
Maximum 26 solenoid valve coils can
be add.
1.2 Round up to 4 bits: different cases:
a) If the number of valve addresses can
be divided by 4 without remainder,
continue with section 1.3.
b) If the number of valve addresses is not
divisible by 4 without remainder, it must
be rounded up to 4 bits because of the
4-bit orientated addressing.
The rounded up 2 bits in the address
range cannot be used.
1.3 Address assignment of the output modules:
The digital outputs are addressed after the
(rounded up 4-bit) addresses of the valves.
Addresses should be assigned in
ascending order without gaps.
Counting should begin on the node
from right to left.
Counting on the individual modules
is from top to bottom.
Digital output modules always occupy
4 addresses.
4-11