Download Print this page

Digital Inputs - Festo FEC Compact Brief Description

Advertisement

Available languages

Available languages

Digital inputs

Number
Number of inputs that can be
used as high-speed counters
(max. 2 kHz)
Input voltage / current
Value for TRUE
Value for FALSE
Input signal delay
Electrical isolation
Permitted length of connecting
cable
Status display with LED
Insulation resistance against in-
ternal system voltage
1)
The input voltages should be generated from electrical circuits from protection class
III. This requirement is fulfilled if the sensor supply voltage is used.
Festo KBS-FEC FC30- 0206NH English
12 / 2 groups; 1 x 4 inputs, 1 x 8
inputs; both groups electrically
isolated from one another. The in-
puts in a group should be either
current-sinking or current-sourc-
ing.
2
24 V DC, input current 7 mA
15 V DC min.
5 V DC max.
typically 5 ms
yes, optocoupler
max. 30 m
yes
Rated voltage of insulation: 50 V
AC
1)
35