3. Installation
PLEASE NOTE
Please note that with common voltage supply
for pin 1 (electronic components and inputs)
and pin 2 (outputs/valves), the lower tolerance
of 10 % for both circuits must be observed.
Check the 24 V operating voltage of the outputs
while your system is operating. Please see that
the operating voltage of the outputs lies within
the permitted tolerances even during full opera-
tion.
Recommendation
Use a closed loop power unit.
Calculate the complete current consumption
according to the following table and select
both a suitable power unit and cable cross
section.
Avoid long distances between the power unit
and the terminal. Calculate the permitted
distance according to Appendix A.
The following rule applies for type 05:
Current
consumption *)
Pin 1
= 2.2 A
Pin 2
= 10 A
V
= 24 V
B
*) Please note that the max. total current
consumption (pins 1 and 2) is 12.2 A.
Cable cross
Distance
section
2
1.5 mm
≤ 14 m
2
2.5 mm
8 m
3-23