Short Circuit/Overload At - Festo FB16 Electronic Manual

Valve terminal type 03/05, field bus connection
Table of Contents

Advertisement

VIFB16 - 03/05
Error
General meaning
category
Internal
Internal errors concern the
errors
general function of a hardware
module or the FIPIO slave.
External
External errors are device-
errors
specific errors which are
registered by the FIPIO field bus
slave.
Logical
Logical errrors refer to
errors
parametrizing errors.
The error messages of internal and logical errors are identical with all
devices/field bus slaves. The valve terminals create device-specific messages
only with external errors.
Fig. 5/14b: Structure of the error categories of the ORPHEE software
Diagnostic
Meaning
information
Short
Monitors the electrical outputs
circuit/
of the output modules.
overload
V
Monitors the supply voltage of
sensors
(V
)
the inputs (sensors).
sen
V
Monitors the operating voltage
outputs
(V
)
of the valves and electrical
out
outputs (no voltage available
e.g. EMERGENCY STOP).
V
Monitors the tolerance of the
valves
(V
)
operating voltage of the valves
val
and electrical outputs.
Fig. 5/14c: Error states of valve terminal
5-22
5. Diagnosis/error treatment
The possible errors are grouped into the follo-
wing three categories in the ORPHEE software:
*)
The diagnostic information of the valve
terminal has the following meaning:
Valve terminal diagnosis
Not relevant
Error entries of the valve
terminal:
EF1 = External error 1 = V
EF2 = External error 2 = V
EF3 = External error 3 = V
EF4 = External error 4 = Sh.
*)
c./o.
Not relevant
Cause
Short circuit
or
overload
Internal fuse triggered
Operating voltage at pin 2 of
operating voltage connection
< 10 V
Operating voltage at pin 2 of
operating voltage connection
< 21.6 V
*)
out
*)
val
*)
sen
0506b

Advertisement

Table of Contents
loading