4. Commissioning

Addressing the outputs

Access to the outputs of valve terminals is
through the ROW objects.
output cyclically at the end of a program.
Addressing is bit-wise or word-wise in accord-
ance with the following rule:
For a bit access:
ROWx,0,y,t
For a word access:
ROWx, 0,y
Note:
Every word or bit of a word can be represented
by a symbol if this has been previously defined
using the station tool "Sdbase".
These objects are
position of the bit in the word:
0 to F in hexadecimal format
Word number: 0 to 7
module number:
always 0 for the valve terminal
address of the valve terminal
on the FIPIO bus:
1 to 62 in decimal format
Word number: 0 to 7
module number:
always 0 for the valve terminal
address of the valve terminal
on the FIPIO bus:
1 to 62 in decimal format