3. Diagnosis

3.4.2 Short circuit/overload at an output module

Deleting procedure
S Set all outputs of the output module to logic
"0" (RESET)
or
S briefly interrupt the CP connection at the CP
output module
or
S briefly interrupt the operating voltage of the
CP system at the field bus node
3-18
If there is a short circuit or overload:
all digital outputs of the module will be switched off,
the green LED "Diag" on the output module will flash
quickly,
the bit short circuit/overload of the diagnostic byte will be
set to "logic 1" (SC/O).
Please note
The outputs cannot be used again until the short circuit or
overload is eliminated and the fault is deleted.
Deleting faults
You can delete a fault by resetting all eight outputs. You can
do this as follows:
Explanation
– Manually or automatically in the program
– Outputs on the output module are reset auto-
matically
– All outputs of the CP system are reset auto-
matically
The outputs can then be set at "logic 1" again.
If the short circuit still exists, the outputs will be switched off
again.
Festo P.BE-CP-FB5-E-EN en 0112a