Parameter Descriptions
Application
Low inertia applications
High inertia applications
3
3
High load at low speed
Table 3.10 Recommendations for FLUX Applications
Adjust starting torque in 1-66 Min. Current at Low Speed.
100% provides nominal torque as starting torque.
54
®
VLT
AutomationDrive Programming Guide
Settings
Keep calculated values
1-66 Min. Current at Low Speed
Increase speed to a value between
default and maximum depending on
application.
Set ramp times matching the
application. Too fast ramp up causes
an overcurrent/overtorque. Too fast
ramp down causes an overvoltage
trip.
1-66 Min. Current at Low Speed
Increase speed to a value between
default and maximum depending on
application.
MG33MG02 - VLT
®
is a registered Danfoss trademark