Troubleshooting
A trip is the action following an alarm. The trip coasts the
motor and is reset by pressing [Reset] or by a digital input
(parameter group 5-1* Digital Inputs [1]). The origin event
that caused an alarm cannot damage the frequency
converter or cause dangerous conditions. A trip lock is an
action when an alarm occurs, which could damage the
frequency converter or connected parts. A trip lock
situation can only be reset by a power cycling.
Bit
Hex
Dec
Alarm Word
Alarm Word Extended Status Word
0
0000000
1
Brake Check
1
(A28)
1
0000000
2
Pwr.card temp
2
(A69)
2
0000000
4
Earth Fault (A14) ServiceTrip,
4
3
0000000
8
Ctrl.Card Temp
8
(A65)
4
0000001
16
Ctrl. Word TO
0
(A17)
5
0000002
32
Over Current
0
(A13)
6
0000004
64
Torque Limit
0
(A12)
7
0000008
128
Motor Th Over
0
(A11)
8
0000010
256
Motor ETR Over
0
(A10)
9
0000020
512
Inverter Overld.
0
(A9)
10
0000040
1024
DC under Volt
0
(A8)
11
0000080
2048
DC over Volt
0
(A7)
12
0000100
4096
Short Circuit
0
(A16)
®
VLT
AutomationDrive Programming Guide
Table 5.2 LED Indication
Alarm Word 2 Warning Word
ServiceTrip,
Brake Check (W28)
Read/Write
ServiceTrip,
Pwr.card temp (A69)
(reserved)
Earth Fault (W14)
Typecode/
Sparepart
ServiceTrip,
Ctrl.Card Temp (W65)
(reserved)
ServiceTrip,
Ctrl. Word TO (W17)
(reserved)
reserved
Over Current (W13)
reserved
Torque Limit (W12)
reserved
Motor Th Over (W11)
reserved
Motor ETR Over (W10) reserved
Discharge High Inverter Overld (W9)
Start Failed
DC under Volt (W8)
Speed Limit
DC over Volt (W7)
External
DC Voltage Low (W6)
Interlock
®
MG33MG02 - VLT
is a registered Danfoss trademark
Warning
Alarm
Trip locked
yellow and red
Warning
Extended
Word 2
Status Word
Start
Ramping
Delayed
Stop
AMA Running
Delayed
reserved
Start CW/CCW
start_possible is
active, when the
DI selections [12]
OR [13] are active
and the requested
direction matches
the reference sign
reserved
Slow Down
slow down
command active,
e.g. via CTW bit
11 or DI
Catch Up
catch up
command active,
e.g. via CTW bit
12 or DI
reserved
Feedback High
feedback > 4-57
reserved
Feedback Low
feedback < 4-56
reserved
Output Current
High
current > 4-51
Output Current
Low
current < 4-50
Discharge
Output Freq High
High
speed > 4-53
Multi-
Output Freq Low
motor
speed < 4-52
underload
Multi-
Brake Check OK
motor
brake test NOT ok
Overload
Compress
Braking Max
or
BrakePower >
Interlock
BrakePowerLimit
(2-12)
yellow
flashing red
Extended
Status Word 2
5
Off
Hand/Auto
Profibus OFF1
active
Profibus OFF2
active
Profibus OFF3
active
Relay 123 active
Start Prevented
Control Ready
Drive Ready
Quick Stop
DC Brake
Stop
Stand by
203
5