Parameter Descriptions
8-43 PCD Read Configuration
Range:
Function:
Size related
[0 - 9999 ] Select the parameters to be assigned
*
to PCD's of the telegrams. The
number of available PCDs depends on
the telegram type. PCDs contain the
actual data values of the selected
parameters.
8-45 BTM Transaction Command
Option:
[0]
Off
[1]
Start Transaction
[2]
Commit transaction
[3]
Clear error
8-46 BTM Transaction Status
Option:
[0]
Off
[1]
Transaction Started
[2]
Transaction Comitting
[3]
Transaction Timeout
[4]
Err. Non-existing Par.
[5]
Err. Par. Out of Range
[6]
Transaction Failed
8-47 BTM Timeout
Range:
60 s
[1 - 360 s]
*
8-48 BTM Maximum Errors
Range:
21
[0 - 21 ]
*
8-49 BTM Error Log
Range:
0.255
[0.000 - 9999.255 ]
*
3.10.5 8-5* Digital/Bus
Parameters for configuring the control word Digital/Bus
merging.
NOTE
These parameters are active only when 8-01 Control Site is
set to [0] Digital and control word.
8-50 Coasting Select
Option:
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
[0] Digital
Activates Start command via a digital input.
input
®
VLT
AutomationDrive Programming Guide
8-50 Coasting Select
Option:
[1] Bus
[2] Logic AND
[3] Logic OR
Function:
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals
(digital input) and/or via the bus.
Option:
[0]
Function:
[1]
[2]
[3]
8-52 DC Brake Select
Option:
Function:
[0] Digital
Function:
8-53 Start Select
Option:
Function:
[0] Digital
[1] Bus
[2] Logic AND
[3] Logic OR
8-54 Reversing Select
Option:
[0] Digital
®
MG33MG02 - VLT
is a registered Danfoss trademark
Function:
Activates Start command via the serial
communication port or fieldbus option.
Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
Digital input
Bus
Logic AND
Logic OR
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTE
Only selection [0] Digital input is available
when 1-10 Motor Construction is set to [1]
PM non-salient SPM.
Activates Start command via a digital input.
input
Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
Activates Start command via a digital input.
input
Activates Start command via the serial
communication port or fieldbus option.
Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
Function:
Select control of the frequency converter
input
reverse function via the terminals (digital input)
and/or via the fieldbus.
3
Function:
117
3