Parameter Descriptions
3.14.4 13-1* RS Flip Flops
The Reset-Set Flip Flops hold the signal until set/reset.
3
3
Par. 13-15
RS-FF Operand S
Par. 13-16
RS-FF Operand R
Illustration 3.51 Reset-Set Flip Flops
Two parameters are used and the output can be used in
the logic rules and as events.
S
R
Flip Flop Output
Illustration 3.52 Flip Flop Outputs
The two operators can be selected from a long list. As a
special case, the same digital input can be used as both
Set and Reset, making it possible to use the same digital
input as start/stop. The following settings can be used to
set up the same digital input as start/stop (example given
with DI32 but is not a requirement).
Parameter
13-00 SL Controller Mode
13-01 Start Event
13-02 Stop Event
13-40 Logic Rule Boolean 1 [0]
13-42 Logic Rule Boolean 2 [0] [2] Running
13-41 Logic Rule Operator 1
[0]
13-40 Logic Rule Boolean 1 [1]
13-42 Logic Rule Boolean 2 [1] [2] Running
13-41 Logic Rule Operator 1
[1]
13-15 RS-FF Operand S [0]
13-16 RS-FF Operand R [0]
126
®
VLT
AutomationDrive Programming Guide
Setting
Notes
On
TRUE
FALSE
[37] Digital
Input DI32
[3] AND
NOT
[37] Digital
Input DI32
[1] AND
[26]
Output from 13-41
Logicrule 0
[0]
[27]
Output from 13-41
Logicrule 1
[1]
®
MG33MG02 - VLT
is a registered Danfoss trademark
Parameter
Setting
[94] RS
13-51 SL Controller Event [0]
Flipflop 0
13-52 SL Controller Action [0]
[22] Run
[27]
13-51 SL Controller Event [1]
Logicrule 1
13-52 SL Controller Action [1]
[24] Stop
Table 3.22 Operators
13-15 RS-FF Operand S
Option:
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[39]
Start command
[40]
Drive stopped
Notes
Output from
evaluating 13-15
and 13-16
Function: