Checking and Saving Parameter Default Values

Use the Verify Menu to check all changes to parameter settings. Refer to
page 117
for details.
Save the verified parameter settings. Change the parameter access level or set a password to the drive to prevent
accidental modification of parameter settings.
u Saving User Default Values: o2-03
Setting o2-03 to 1 saves the current modified parameter settings as default values, then resets o2-03 to 0. The drive can
now recall all the saved parameter values by performing a User Initialization (A1-03 = 1110). The saved settings can be
initialized/restored as needed. Saving the User Parameter settings will cause selection 1110 (User Initialize) to appear as
a selection for parameter A1-03 (Initialization). It is now possible to initialize/restore the saved settings. In addition,
setting o2-03 to 2 (Clear All) clears the User default values, and "1110" is hidden from the selection for A1-03.
No.
Name
o2-03
Saving User Defaults
A1-03
Initialize Parameters
u Parameter Access Level: A1-01
Setting the Access Level for "Operation Only" (A1-01 = 0) allows the user to access parameters A1-
only. Other parameters are not displayed.
Setting the Access Level for "User Parameters" (A1-01 = 1) allows the user to access only the parameters that have been
previously saved as User Parameters. This is helpful when displaying only the relevant parameters for a specific
application. The saved User Parameters can be displayed in the Set-up Mode.
No.
Name
A1-01
Access Level of Parameter
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions

4.9 Checking and Saving Parameter Default Values

Description
Saves/clears the default values used for A1-03 (Initialize
Parameters).
0: Saved/Not Set
1: Set Defaults. Saves the current parameter settings as default
values so a User Initialization can be performed to recall
settings.
2: Clear All. Clears the current default values that have been
saved.
After default values are saved, it is possible to select setting
1110 (User initialize) in A1-03 (Initialize Parameters).
Selects a method to initialize the parameter.
0: No initializing
1110: User initialize
(User parameter setting values must have been saved using
o2-03.)
2220: Initialization with 2-wire sequence
(Sets the parameters to default setting.)
Description
Selects the access level for parameters (for setting and
monitoring).
0: Operation only
(Sets and monitor A1-00 and A1-04. U -
also be monitored.)
1: User parameters
(Only the parameters A2-01 to A2-16 for each application and
the recently changed parameters A2-17 to A2-32 can be set
and monitored.)
2: Advanced Access
(Can set and monitor all parameters)
Verifying Parameter Changes: Verify Menu on
Setting
Range
0 to 2
0 to 5550
Setting
Range
parameters can
0 to 2
Default
0
0
and U -
Default
4
2
133