◆ Switching Between LOCAL and REMOTE

Entering the run command using the LED operator is referred to as LOCAL, while entering the run command from an
external device via the control circuit terminals or network option card is referred to as REMOTE.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating
machinery and electrical connections prior to switching between LOCAL mode and REMOTE mode.
There are two ways to switch between LOCAL and REMOTE.
Note: 1. After selecting LOCAL, the LO/RE light will remain lit.
2. The drive will not allow the user to switch between LOCAL and REMOTE during run.
Using the LO/RE Key on the LED Operator
1.
Turn on the power to the drive. The initial display appears.
Press
. The LO/RE light will light up. The drive is now in Local.
2.
To set the drive for REMOTE operation, press the
Using Input Terminals S1 through S6 to Switch between LO/RE
Switch between LOCAL and REMOTE using one of the digital input terminals S1 through S6 (set the corresponding
parameter H1-01 through H1-06 to "1").
Follow the example below to set the digital input terminals.
Note: 1. For a list of digital input selections,
2. Setting a multi-function input terminal to a value of 1 disables the LO/RE key on the LED operator.

◆ Parameters Available in the Setup Group

Setup Mode (STUP)
Parameters used for this drive are classified into A to U. To simplify the drive setup, frequently used parameters are
selected and input into Setup Mode.
1.
To set a parameter, the Setup Mode must be displayed first. Press the Up/Down key until
2.
Select the parameter and change the setting.
desired parameter cannot be set in the Setup mode, use the Parameter Setting mode.
Note: When parameter A1-02 (Control Method Selection) is changed, some parameter set values are also changed automatically.
Note: Use the "Par" menu in the Programming mode to access parameters not listed in the Setup Group.
Parameter
A1-02
Control Method Selection
b1-01
Frequency Reference Source 1
b1-02
Run Command Source 1
b1-03
Stop Method Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-01
Duty Selection
C6-02
Carrier Frequency Selection
d1-01
Frequency Reference 1
d1-02
Frequency Reference 2
d1-03
Frequency Reference 3
d1-04
Frequency Reference 4
d1-17
Jog Frequency Reference
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Step
key again.
Refer to Parameter List on page
Table 4.4
Table 4.4 Setup Group Parameters
Name
4.3 The Drive and Programming Modes
317.
lists parameters available in the Setup group. If the
Parameter
E1-01
Input Voltage Reference
E1-03
V/f Pattern Selection
E1-04
Maximum Output Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
E1-09
Minimum Output Frequency
E1-13
Base Voltage
E2-01
Motor Rated Current
E2-04
Number of Motor Poles
E2-11
Motor Rate Capacity
H4-02
Terminal AM Gain Setting
L1-01
Motor Protection Function Selection
L3-04
Stall Prevention Selection during Deceleration
Display/Result
STOP
is displayed.
Name
4
83