Wiring Conforming to EMC Directives

Conformance to the EMC Directives (EN 55011 Class A Group 1 (EMI) and EN 61000-6-2 (EMS)) can
be ensured by wiring under the conditions described in this section.
These conditions are for conformance of OMNUC G5-series (Pulse-train Input Type) products to the
EMC directives. EMC-related performance of these products, however, may be influenced by the
configuration, wiring, and other conditions of the equipment in which the products are installed. The
EMC conformance of the system as a whole must be confirmed by the customer.
The following are the requirements for EMC Directive conformance.
• The Servo Drive must be installed in a metal case (control panel). (The motor does not, however,
have to be covered with a metal plate.)
• Noise filters and lightening surge absorptive elements (surge absorbers) must be installed on power
supply lines.
• Braided shielded cables must be used for encoder cables. (Use tin-plated, mild steel wires for the shielding.)
• All cables, I/O wiring, and power lines connected to the Servo Drive must have clamp cores installed.
• The shields of all cables must be directly connected to a ground plate.
4-3-1

Wiring Method

R88D-KP01H/-KP02H/-KP04H/-KP08H/-KP10H/-KP15H/-KP20H/-KP30H/-KP50H
Single-phase: 100 VAC
3-phase: 200 VAC
FC2
SG
Single-phase:
100 VAC
• For models with a single-phase power supply input (R88D-KP01H/-KP02H/-KP04H/-KP08H/-KP10H/
-KP15H), the main circuit power supply input terminals are L1 and L3.
• Ground the motor's frame to the machine ground when the motor is on a movable shaft.
• Use a ground plate for the frame ground for each unit, as shown in the above diagrams, and ground
to a single point.
• Use ground lines with a minimum thickness of 3.5 mm
lines are as short as possible.
• A no-fuse breaker, surge absorber, and noise filter should be positioned near the input terminal block
(ground plate), and I/O lines should be separated and wired at the shortest distance.
4 - 20
(2)
FC1
(1)
NF
(6)
(5)
Controller
(8)
OMNUC G5-series (Pulse-train Input Type) AC Servomotors and Servo Drives User's Manual
SD
U
L1
CNA
V
L2
CNB
W
L3
L1C
L2C
CN2
FC1
CN1
(7)
2
, and arrange the wiring so that the ground
(3)
FC3
(4)
FC1
SM

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G5 r88d-ke seriesG5 r88m-kp series

Table of Contents