4-3 Wiring Conforming to EMC Directives

4-3 Wiring Conforming to EMC Directives

Conformance to the EMC directives (EN55011 Class A Group 1 (EMI) and EN61000-6-2
(EMS)) can be ensured by wiring under the conditions described in this section.
These conditions are for conformance of OMNUC G5-Series products to the EMC directives.
EMC-related performance of these products, however, may be influenced by the configuration,
wiring, and other conditions of the equipment in which the products are installed. The EMC
conformance of the system as a whole must be confirmed by the customer.
The following are the requirements for EMC directive conformance.
 The Servo Drive must be installed in a metal case (control panel). (The motor does not, however,
have to be covered with a metal plate.)
 Noise filters and lightening surge absorptive elements (surge absorbers) must be installed on power supply lines.
 Braided shielded cables must be used for all encoder cables. (Use tin-plated, mild steel wires for
the shielding.)
 All cables, I/O wiring, and power lines connected to the Servo Drive may have clamp cores
installed to improve the noise immunity.
 The shields of all cables must be directly connected to a ground plate.
4

Wiring Method

R88D-KNA5L-ML2/-KN01L-ML2/-KN02L-ML2/-KN04L-ML2/-KN01H-ML2/-KN02H-ML2/
-KN04H-ML2/-KN08H-ML2/-KN10H-ML2/-KN15H-ML2/-KN20H-ML2/-KN30H-ML2/-KN50H-ML2
Single-phase: 100 VAC
3-phase: 200 VAC
Single-phase:
100 VAC
*1. For models with a single-phase power supply input (R88D-KNA5L-ML2/-KN01L-ML2/-KN02L-ML2/-
 Ground the motor's frame to the machine ground when the motor is on a movable shaft.
 Use a ground plate for the frame ground for each unit, as shown in the above diagrams, and ground to a single point.
 Use ground lines with a minimum thickness of 3.5 mm
lines are as short as possible.
 No-fuse breaker, surge absorber, and noise filter should be positioned near the input terminal
block (ground plate), and I/O lines should be separated and wired at the shortest distance.
4-21
(2)
(1)
FC2
NF
(6)
SG
(5)
TB
(8)
Controller
KN04L-ML2/-KN01H-ML2/-KN02H-ML2/-KN04H-ML2/-KN08H-ML2), the main circuit power supply
input terminals are L1 and L3.
OMNUC G5-Series AC Servo Drives Users Manual (Built-in MECHATROLINK-II communications type)
SD
U
L1
CNA
V
L2
CNB
L3
W
L1C
L2C
CN2
FC1
CN1
(7)
2
, and arrange the wiring so that the ground
(3)
FC3
(4)
FC1
SM

Advertisement

Table of Contents
loading

This manual is also suitable for:

R88m-k seriesOmnuc g5 series

Table of Contents