1: Selecting 5824 Options; 5880 Led I/O Module - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

Control Panel Installation
4.
Configure the 5824 device through programming. See Section 4.12.1 below.
4.12.1 Selecting 5824 Options
Configuring the 5824 includes the following steps:
1.
Add the module to the system. JumpStart will add the module automatically (see Section 7.1). You can also add it manually. See
Section 8.2.2.
2.
Select a name, if desired (see "Naming Modules" on page 91).
3.
Select options for the printer and the output port.
Printer and Output Port Options
1.
From the Main Menu, select 7 for Panel Programming.
2.
Select 1 for Module.
3.
Select 1 for Edit Module.
4.
From the list that displays, select the 5824 module you want to configure.
5.
Press right arrow twice to skip over the Enter Module ID and Enter Module Name options. A screen similar to the one shown in
Figure 4.33 will display.
6.
Select options for the printer as needed for your installation. Most printers are parallel.
7.
If you are using a serial printer, use the next screen to select serial port options as required for your printer. Refer to your printer manual
if you need more information.

4.13 5880 LED I/O Module

The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with most customized floor plan
annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller. The 5880 also has eight inputs for dry contact monitor-
ing. When used with the 6820EVS, the 5880 inputs can be programmed to replicate the eight EVS buttons located on the front of the voice
control module. A maximum of eight 5880 modules can be used in the system. The following sub-sections describe hardware installation.
Refer to Section 8 for programming information.
44
FACP
supervised,
power-limited
EXT. COMM
Figure 4.32 5824 Connection to the Panel
Monitor Printer=Yes
Output Port=Parallel
Event Logging=NO
More
Figure 4.33 Selecting Printer and Output Port Options
Option
Baud Rate:
Data Bits:
Stop Bits:
Parity:
Table 4.5 Serial Printer Options
DIP switches
5824
Select Yes if printer should be supervised for
Out-of-Paper and Offline conditions.
Select type of printer, Parallel or Serial.
Choices
75 - 19200
5 - 8
0.5, 1, 2
None, Even, Odd
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
5880 LED I/O Module
parallel
connectors for
connection to
printer
serial

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820evs

Table of Contents