Installation of Optional Modules

4XLMF LED Interface Module (Flex 404 only)

The 4XLMF supports the RZA-4XF Remote Annunciator module. The wiring of this module must
follow the requirements as specified in "Power-limited Wiring Requirements" on page 23.
Important: The 4XLMF module can only be installed on connectors J3 and J5 of the Flex 404
main circuit board.
4XLB
4XLMF Module
Front View of RZA-4XF
Flex 402 & Flex 404 Instruction Manual — P/N 52194:D4 3/27/2015
+24 VDC
1
Out #1
2
Out #2
3
Out #3
4
Out #4
5
System Trouble
6
Sound
7
Resound
8
Connect to corresponding terminals of
Figure 2.15 4XLMF LED Interface Module
RZA-4XF Remote Annunciator
Note: Make wiring connections with system
power off. Maximum wire impedance is
50 ohms per wiring connection.
Side View
Installation
Single-gang Box
29